WEBVTT

1
00:00:00.550 --> 00:00:03.240
This vibration monitor uses an IRIV IO

2
00:00:03.240 --> 00:00:06.779
Controller, running the Wilcoxon gateway firmware.

3
00:00:06.779 --> 00:00:08.832
It reads a Wilcoxon 883M, and

4
00:00:08.832 --> 00:00:11.663
publishes to Viking Analytics over MQTT.

5
00:00:12.883 --> 00:00:14.253
The sensor measures.

6
00:00:14.253 --> 00:00:16.856
The controller polls it and publishes.

7
00:00:16.856 --> 00:00:19.321
Viking Analytics learns the machine,

8
00:00:19.321 --> 00:00:20.897
and flags what changes.

9
00:00:22.117 --> 00:00:24.116
This simplified cutaway reveals the

10
00:00:24.116 --> 00:00:26.058
bearings, shaft and pump impeller.

11
00:00:26.058 --> 00:00:29.143
Forces from rotating parts travel through the bearings

12
00:00:29.143 --> 00:00:32.227
into the housing, where the sensor measures vibration.

13
00:00:32.227 --> 00:00:34.398
The motion is slowed for illustration;

14
00:00:34.398 --> 00:00:35.769
this is not a drawing of

15
00:00:35.769 --> 00:00:37.197
a specific motor or pump.

16
00:00:38.467 --> 00:00:40.400
The 883M sits on the motor, and

17
00:00:40.400 --> 00:00:43.581
measures vibration on three axes, plus temperature.

18
00:00:44.367 --> 00:00:46.617
The controller polls it over Modbus,

19
00:00:46.617 --> 00:00:48.804
and publishes each reading as MQTT.

20
00:00:49.667 --> 00:00:51.808
MultiViz learns what normal looks like.

21
00:00:53.417 --> 00:00:56.050
The Wilcoxon 883M measures vibration in

22
00:00:56.050 --> 00:00:58.007
X, Y and Z, plus temperature.

23
00:00:58.007 --> 00:01:01.856
It reports acceleration, velocity and displacement, along

24
00:01:01.856 --> 00:01:04.556
with waveforms and a frequency spectrum.

25
00:01:04.556 --> 00:01:07.189
Its acceleration range is plus or minus

26
00:01:07.189 --> 00:01:09.957
sixteen g, with a frequency response from

27
00:01:09.957 --> 00:01:10.902
2 Hz to 5 kHz.

28
00:01:10.902 --> 00:01:13.197
The compact housing is thirty five

29
00:01:13.197 --> 00:01:16.100
millimetres wide and twenty six millimetres

30
00:01:16.100 --> 00:01:18.261
high, with an M eight connector.

31
00:01:18.261 --> 00:01:20.286
It sends digital readings over

32
00:01:20.286 --> 00:01:21.164
Modbus R T U.

33
00:01:21.164 --> 00:01:24.607
These measurements help track changes in a machine;

34
00:01:24.607 --> 00:01:28.522
diagnosis also needs its operating conditions and history.

35
00:01:29.750 --> 00:01:31.597
Its RS485 pair lands on A

36
00:01:31.597 --> 00:01:33.370
and B, with ground on G.

37
00:01:33.370 --> 00:01:35.659
The controller ends the bus, so

38
00:01:35.659 --> 00:01:37.875
the terminator switch goes on.

39
00:01:39.083 --> 00:01:41.269
A 24 V supply powers the controller,

40
00:01:41.269 --> 00:01:43.455
and the sensor shares the same rail.

41
00:01:45.083 --> 00:01:47.246
The controller also has two

42
00:01:47.246 --> 00:01:49.409
analog inputs, AN0 and AN1.

43
00:01:49.409 --> 00:01:52.613
Each can read a Wilcoxon PCC420V, a loop

44
00:01:52.613 --> 00:01:56.378
powered vibration sensor with a 4–20 mA output.

45
00:01:56.378 --> 00:01:58.621
Here, one sits on the motor,

46
00:01:58.621 --> 00:02:00.223
and one on the pump.

47
00:02:01.450 --> 00:02:04.441
Set each input's mode switch to Current.

48
00:02:04.441 --> 00:02:06.535
The loop runs from a 12–30 V

49
00:02:06.535 --> 00:02:09.452
supply, through the sensor, into AN0 or

50
00:02:09.452 --> 00:02:12.368
AN1, and back from analog ground, AGND.

51
00:02:12.368 --> 00:02:15.659
Take the sensor's pinout from its datasheet.

52
00:02:16.883 --> 00:02:20.097
Choose each sensor's model in the I/O settings.

53
00:02:20.097 --> 00:02:22.148
Four milliamps reads zero, and

54
00:02:22.148 --> 00:02:24.472
twenty milliamps reads full scale.

55
00:02:24.472 --> 00:02:27.343
Both readings appear on the dashboard, and

56
00:02:27.343 --> 00:02:29.258
go out over MQTT and Modbus.

57
00:02:29.258 --> 00:02:31.377
A broken loop shows as a fault.

58
00:02:32.583 --> 00:02:35.182
Install the firmware from the web installer.

59
00:02:35.182 --> 00:02:37.426
Then set the MQTT broker and the alarm

60
00:02:37.426 --> 00:02:40.084
limits in the controller's own web dashboard.

61
00:02:41.317 --> 00:02:43.724
MultiViz learns a baseline for each sensor,

62
00:02:43.724 --> 00:02:45.684
so there are no thresholds to tune.

63
00:02:45.684 --> 00:02:48.260
When the pattern shifts, it names the symptom,

64
00:02:48.260 --> 00:02:50.836
and ranks which machine needs attention first.

65
00:02:52.050 --> 00:02:53.012
Now the alarm.

66
00:02:53.012 --> 00:02:55.761
Output zero follows the dashboard alarm,

67
00:02:55.761 --> 00:02:57.342
and drives a 24 V relay

68
00:02:57.342 --> 00:02:58.991
for a beacon and buzzer.

69
00:03:00.217 --> 00:03:01.665
A push button on input

70
00:03:01.665 --> 00:03:03.442
one acknowledges the alarm.

71
00:03:03.442 --> 00:03:05.482
Input zero can start a capture.

72
00:03:06.733 --> 00:03:08.350
Vibration on the motor climbs

73
00:03:08.350 --> 00:03:09.520
past the alarm limit.

74
00:03:10.533 --> 00:03:13.617
After the delay, the controller trips the alarm.

75
00:03:13.617 --> 00:03:15.480
Output zero closes the relay,

76
00:03:15.480 --> 00:03:16.958
and the beacon flashes.

77
00:03:17.733 --> 00:03:19.883
The operator presses acknowledge.

78
00:03:19.883 --> 00:03:21.838
While vibration is still high,

79
00:03:21.838 --> 00:03:23.075
the relay stays on.

80
00:03:23.733 --> 00:03:25.527
Once it clears, the relay drops,

81
00:03:25.527 --> 00:03:27.153
and the alarm is ready again.

82
00:03:28.683 --> 00:03:30.588
The rule runs on the controller.

83
00:03:30.588 --> 00:03:32.850
Trip on velocity or temperature, after

84
00:03:32.850 --> 00:03:34.576
a delay, and latch the relay.

85
00:03:34.576 --> 00:03:36.422
It drops only when the alarm is

86
00:03:36.422 --> 00:03:38.922
acknowledged, and the reading has cleared.

87
00:03:40.150 --> 00:03:41.597
Sense, analyse, act.

88
00:03:41.597 --> 00:03:44.129
One controller, its sensors, and an

89
00:03:44.129 --> 00:03:46.517
alarm that someone has to answer.