Machine condition monitoring

Vibration in.
Alarm out.

See a Wilcoxon 883M on a motor, an IRIV IO Controller reading it over RS485, and a local alarm that someone can acknowledge. Follow the data into Viking Analytics over MQTT.

Real product references · narrated 3D demonstration · interactive wiring

Wilcoxon 883M sensor with side M8 connector
Wilcoxon 883MVibration and temperature
IRIV IO Controller MQTT Gateway with orange terminal blocks
IRIV IO ControllerRS485 to MQTT and alarm I/O
SenseWilcoxon 883M3-axis vibration + temperature
BridgeIRIV IO ControllerGateway firmware · dashboard
AnalyseViking AnalyticsMultiViz baselines + symptoms
DO0 → 24 V relay → beacon + buzzerDI1 ← acknowledge push button

The film

How it works.

Follow the sensor, the wiring, the firmware setup, MultiViz and one complete alarm event.

English narration · short captions · 1080p.

Read the narration transcript

Live

Watch your machine live.

Connect to the MQTT broker the gateway publishes to and this panel shows its real readings, relay and buttons as they arrive. It only listens and never sends commands.

Not connectedSensor -- · last reading -- · uptime --
Velocity RMS · X-- mm/s
Velocity RMS · Y-- mm/s
Velocity RMS · Z-- mm/s
Temperature-- °C
Velocity RMS trend, 10 Hz – 1 kHz · X Y Z · mm/s
Cabinet
Alarm
--
DO0 relay
--
DI1 acknowledge
--
DI0 capture
--
Sensor
--
Latch
--

The browser needs the broker's WebSocket port (on this https page, wss://), not port 1883. Use a login that can only subscribe to the base topic. The password is never saved.

Try the alarm

Push the motor. Acknowledge it.

Drag the velocity past 4.5 mm/s. DO0 turns on and stays latched. It drops only once the alarm is acknowledged on DI1 and the reading is back under the limit, in either order. This is the same logic the firmware runs.

883M · velocity RMS, X axis

2.0mm/sZone B · fine
02.8 warning4.5 alarm8 mm/s

Published to MQTT

Move the slider to publish a reading.

Cabinet

NORMAL
DO0 off · relay open · beacon off
DI1 · acknowledge push button
The USER button and the dashboard can acknowledge too.

The firmware also applies the delay and hysteresis you set. Both are zero here.

Wiring

From motor to action.

Three paths make the system work: sensor readings, network data, and a local alarm circuit.

01 · Sense883M → IOCPower and Modbus RTU run from the motor-mounted sensor to the controller. Match the cable pins to V+V−ABG.
02 · PublishIOC → MQTTThe controller sends measurements through Ethernet to the broker. Viking Analytics receives the sensor data there.
03 · RespondDO0 → relay → beaconDO0 switches a relay for the local alarm. The acknowledge push button returns to DI1.

Simplified view for orientation. Use the terminal-by-terminal table and the device documentation when wiring hardware.

FromToNotes
24 V PSU +IOC V+, 883M pin 1 (power)IOC takes 10–30 V DC, the 883M 6–24 V DC. Keep the rail at 24.0 V, not above.
24 V PSU −IOC V−, 883M pin 2 (ground)Common 0 V.
883M pin 3 (signal +)IOC RS485 AUse 4-conductor shielded cable with an M8 4-pin plug, keeping signal + and − on one twisted pair.
883M pin 4 (signal −)IOC RS485 BIf there are no replies, swap A and B first.
883M ground (0 V)IOC RS485 GGives the isolated port its reference. Termination switch: 120 Ω ON (the IOC ends the bus).
Cable shieldCabinet earth, one end onlyThe 883M ties the shield to its housing (pin 5).
24 V +IOC DO0 (first terminal)DO0 is a solid-state output on its own pair of terminals, rated 50 V / 500 mA.
IOC DO0 (second terminal)Relay coil A1; A2 to 0 VUse a 24 V DC relay and fit a flyback diode across the coil.
Relay NO contactBeacon + buzzerThe relay contact carries the beacon's current, not the IOC output.
24 V + → push button (NO)IOC DI1Wire S/S0..4 to 0 V so DI1 sees +24 V when pressed. A rising edge acknowledges.
Optional buttonIOC DI0A rising edge starts an X/Y/Z waveform capture.
IOC EthernetSite network → MQTT broker → Viking AnalyticsPlain MQTT on port 1883. See the TLS note below.

Scaling the installation

One RS485 bus. Multiple sensor addresses.

Connect the sensors through the IOC’s RS485 A, B and G terminals. Each sensor needs a unique Modbus address and matching serial settings. The controller polls addresses in turn.

Expansion concept · not enabled by this demo firmware

Can one IOC monitor 32 sensors?

The current custom 883M gateway reads one configured sensor ID. A 32-sensor installation needs a firmware polling list, separate readings and alarms per sensor, and testing of power, bus loading and refresh time. Changing the diagram does not enable that capability.

Proposed multi-sensor RS485 trunk One IOC at the first end connects along an A and B trunk to sensors with unique addresses 1, 2 through N. Short branches connect each sensor. Termination is at the two physical ends. G and a separately sized power supply are required but omitted from this signal diagram. N equals 32 only after firmware and installation validation. IRIV IOCA / B / GA → pin 3 (+)B → pin 4 (−)883M · ID 1883M · ID 2883M · ID N…Termination at both physical ends · short branches · G and power omitted for clarity
01 · WireA, B and referenceRoute one trunk with short branches: A to pin 3, B to pin 4, G to sensor ground. Use a correctly sized supply for pin 1 and pin 2. Terminate the two physical bus ends, not every sensor.
02 · AddressConfigure each sensorAssign unique IDs, for example 1–32, one sensor at a time. Match baud, parity and stop bits. For a star layout, use an appropriate RS485 hub as described by Wilcoxon.
03 · ValidateAllow time for every replyMore sensors and waveform transfers share the same bus time. Verify refresh time, missing-sensor handling and per-sensor MQTT identification before deploying.

32 polling jobs is a separate limit. Cytron’s standard IOC MQTT firmware offers up to 32 poll jobs. One sensor may need several jobs, so this does not guarantee complete monitoring of 32 vibration sensors.

References: Cytron poll-job documentation · Wilcoxon bus topologies and settings · Custom gateway source reviewed.

Setup

Install, connect, set the alarm.

01 · Firmware

Web installer

  • On the web installer, choose 883M, then IRIV IO Controller, and download the .uf2 file.
  • Plug in USB-C, hold BOOT, press RESET, release BOOT, then copy the file to the RP2350 drive.
  • Wire the sensor to RS485 A, B and G.
02 · MQTT

To Viking Analytics

  • In the gateway's web dashboard, enter the broker host, port 1883, and the user and password from Viking Analytics.
  • Base topic 883M: metrics, waveforms and spectra. Status goes to 883M/status and I/O to 883M/io.
  • MultiViz learns a baseline per sensor, so there are no thresholds to set there.
03 · Alarm

Dashboard + IOC I/O

  • Set the velocity RMS and temperature limits, and the delay, in the dashboard.
  • Under Settings › IOC I/O, DO0 follows the dashboard alarm, latched (this is the default). DO1 follows sensor faults.
  • DI1 acknowledges and DI0 starts a capture.
TopicDirectionContent
883MGateway → brokerMetrics, waveform chunks and spectrum chunks
883M/statusGateway → brokerHealth status, normally every five minutes
883M/ioGateway → brokerio_status: inputs, outputs, latched and acknowledged, on every change and at least once a minute
883M/commandBroker → gatewayCommands such as trigger_all and get_metrics, with the sensor serial number
Good to know
  • On the IRIV IO Controller, MQTT runs over plain port 1883 only, with no TLS. If the Viking broker needs TLS, forward through a local broker.
  • IOC I/O (DO0–DO3, DI0–DI10, AN0/AN1) is in beta and not yet validated on hardware. Test the alarm chain before relying on it.
  • One IRIV IO Controller reads one 883M.
  • 4.5 mm/s is a starting point: the ISO 10816-3 alarm line for a medium machine on a rigid foundation, with 2.8 mm/s as the warning line. Set it for your machine.

Wilcoxon 883M

The sensor on the motor.

A supported cable, from sensor to cabinet

The film shows a seated M8 plug, a flexible boot, a service bend, cable clamps and a protected conduit run into the cabinet gland. This is an illustrative route; select the cable’s bend radius and supports for the actual installation.

Wilcoxon’s optional cable uses red for power, black for ground, green for signal + and white for signal −. The shield connects through the connector housing. Check your cable’s pinout before wiring.

883M setup manual · connector and cable definitions ↗

Read the official Wilcoxon 883M datasheet (PDF) ↗

MeasuresThree axes + temperatureTrack vibration in X, Y and Z at the mounting point.
ReportsMetrics, waveform, spectrumRead acceleration, velocity and displacement, or inspect the signal over time and frequency.
Helps explainChanges in machine conditionCompare readings with the machine’s operating conditions and history before diagnosing a fault.

A digital triaxial MEMS accelerometer with a temperature sensor. It works out the vibration numbers itself and serves them over Modbus RTU, so the IOC only has to read registers.

Wilcoxon 883M sensor: black aluminium top, stainless base, M8 connector on the side
Aluminium top, stainless base, M8 connector and an RGB status LED.
Wilcoxon 883M side view with X, Y and Z axis markings, on the magnet mount adapter
The X, Y, Z axes are marked on the side. Shown on the MD883 magnet adapter.

Dynamic

Acceleration range
±16 g peak
Resolution
0.488 mg
Frequency response (±3 dB)
2 Hz – 5 kHz
Resonance
6.9 kHz

Communication

Interface
RS485
Protocol
Modbus RTU
Recommended baud
9,600 or 115,200 bps
Max. baud
921,600 bps
Functions
03 / 04 read · 06 / 10 write · 2B device ID
Max. per request
125 registers

Other outputs

Temperature
−20 to +70 °C
True peak
Sampled at 13.333 kHz
Spectrum
0 – 5 kHz, 6,145 lines
Time waveform
13,333 samples, 1 s
Also
Crest factor, standard deviation

Electrical & build

Power
6 – 24 V DC
Indicator
1 RGB LED
Size · weight
35 mm dia. × 26 mm · 75 g
Case
6061 aluminium top, 303 stainless base
Sealing
IP67 · 5–95 % RH
Storage
−20 to +80 °C

Calculated metrics, for each of X, Y and Z

MetricRMS bandsPeak bands
Acceleration2 Hz – 1 kHz · 10 Hz – 5 kHz2 Hz – 1 kHz · 10 Hz – 5 kHz
Velocity10 Hz – 1 kHz · 10 Hz – 5 kHz10 Hz – 1 kHz · 10 Hz – 5 kHz
Displacement2 Hz – 1 kHz · 10 Hz – 1 kHz2 Hz – 1 kHz · 10 Hz – 1 kHz

The bands follow ISO 10816-3 and ISO 20816-3.

M8 connector pins

Pin 1
Power, 6–24 V DC
Pin 2
Ground
Pin 3
Signal + (RS485)
Pin 4
Signal − (RS485)
Pin 5
Shield (housing)

Mounting

Adhesive
On the flat base
Screw
SF883 screw pad adapter
Magnet
MD883 magnet adapter
Why an adapter
Fixes the axis orientation and the cable exit

Made for

Rotating
Motors, fans, pumps, compressors
Drive train
Gearboxes, couplings, bearings
Plant
CNC, conveyors, HVAC, cranes
Wire colours depend on the M8 cable you use (Wilcoxon sells the RM8 cable), so match them to the pin numbers above.